Configuration; Configuring The Module Via Ethernet/Ip; Selecting The Module; Selecting A Connection - WAGO 765-1505/100-000 Product Manual

I/o system field 8-channel digital input/output; ethernet/ip; 24 v dc; 2.0 a; 8 × m8 connection
Table of Contents

Advertisement

765-1505/100-000
8. Then run the RunStandAlone.bat file.
ð The DHCP server is now ready.
ð In the output window, Open DHCP Server shows the query and the assigned IP ad-
dress.

10.2 Configuration

10.2.1 Configuring the Module via EtherNet/IP

For the EtherNet/IP scanner and EtherNet/IP adapter to exchange process data, you
need to configure the EtherNet/IP scanner. This requires the device description file (EDS
file) for the module used:
• wago_07651505.eds
Carry out the following steps in the configuration software of the EtherNet/IP scanner
used:
• Import the EDS file.
• Select the module from the device catalog.
• Add the module to the configuration project.
• Select a connection: connection 1, connection 2 etc.
• Set the parameters.
The individual steps are describe in detail below.

10.2.1.1 Selecting the Module

Select the module used from the device catalog.
Module: 765-1505/100-000
Designation:8 DIO FLD EI 24 VDC 2.0 A

10.2.1.2 Selecting a Connection

The module offers multiple connections. Select a connection for your application. By se-
lecting the connection, you determine the following:
• Connection type: "Exclusive owner," "Input only" or "Listen only"
• Whether or not the scanner transfers the port parameters to the product
Connection Type
The module offers multiple connection types:
• Input only: The scanner can only read input process data. This is the default connec-
tion type.
• Listen only: The scanner can only read input process data. This connection type re-
quires another scanner that establishes an "Input only" connection to the product.
Product manual | Version: 2.0.0
8DIO FLD EI DC 24V 2.0A
Commissioning
57