Stored data (SD) operation
Manual sequential operation
Operation based on the operation data number set in the next data number is executed whenever the SSTART input
is turned ON. This is a convenient method when multiple positioning operations are performed sequentially because
there is no need to repeatedly select each operation data number.
• Even if operation of the operation data number for which the manual sequential operation is set is
completed, the SEQ-BSY output is not turned OFF (manual sequential waiting status). If the SSTART
input is turned ON in a state where the SEQ-BSY output is ON, the operation data number set in
the next data number is executed.
• If the SSTART input is turned ON in a state where the SEQ-BSY output is OFF, the operation data
number presently selected is executed.
z Example of use:
When positioning operation is performed to multiple coordinates at a desired time
Setting the operation data
Data
Operation type
No.
Absolute
No. 0
positioning
Absolute
No. 1
positioning
Absolute
No. 2
positioning
Operation example
Speed
2,000
1,500
No.0
500
300
0
100
1,000
–500
–1,500
46
Position
Speed
[step]
[Hz]
1,000
1,500
2,000
2,000
300
1,500
No.1
2,000
Position
No.2
SSTART input
Starting/
Stopping
changing rate
deceleration
[kHz/s]
[kHz/s]
15.000
15.000
20.000
20.000
10.000
10.000
Speed
2,000
1,500
No.0
500
0
-500
–1,500
START input
Next data
Link
number
Manual
↓ (+1)
sequential
Manual
↓ (+1)
sequential
No link
Stop
No.1
Time
No.2