z ZV output
When the feedback speed is equal to or less than the speed set in the "ZV detection speed range" parameter with the
operating speed 0 r/min as a center, the ZV output is turned ON.
Feedback speed
Operating speed: 0 r/min
ON
ZV output
OFF
Related parameters
MEXE02
Name
code
ZV detection speed
p7
range
z OL-DTCT output
The OL-DTCT output is turned ON when the output torque reaches the torque to detect the overload alarm.
Refer to p.263 for detection of the overload alarm.
Stored data operation status indication
z SEQ-BSY output
The SEQ-BSY output is turned ON while stored data operation is performed.
z DELAY-BSY output
The DELAY-BSY output is turned ON when the driver is in a state of the waiting time after operation (drive-complete
delay time) or the standby state (Dwell).
Direct data operation status indication
z DCMD-FULL output
The DCMD-FULL output is turned ON when data is being written to the buffer area of direct data operation.
z DCMD-RDY output
This signal is output when the driver is ready to start direct data operation.
The DCMD-RDY output is turned ON when all of the following conditions are satisfied.
• The control power supply and the main power supply of the driver are turned on.
• The S-ON input is ON.
• The STOP input is OFF.
• The STOP-SOFF input is OFF
• The CLR input is OFF.
• An alarm is not being generated.
• Return-to-home operation or macro operation is not executed.
• The following monitors or menus are not executed with the MEXE02 software.
− Teaching, remote operation
− I/O test
− Data writing
− Reset
• The following commands are not executed via EtherNet/IP.
− Configuration
− Batch data initialization
− All data batch initialization
− Read batch NV memory
− Write batch NV memory
− Read from backup
− Write to backup
ZV detection speed range
Description
Sets the output range (one side) of the ZV output
with the operating speed 0 r/min as a center.
Output signals
Initial
Setting range
value
0 to 200 r/min
15