8.4.2 Advanced Autotuning by Reference Procedure

The following procedure is used for advanced autotuning by reference.
Always set the moment of inertia ratio before you execute autotuning with a host reference.
• If you use phase control with an MP2000-series Controller, set the mode selection to 1. If the mode selec-
tion is set to 2 or 3, correct phase control may not be possible.
(1) Procedure for Autotuning with a Host Reference
Use the following procedure.
1.
Confirm that the correct moment of inertia ratio in Pn103 is set by using the advanced
autotuning.
2.
In the SigmaWin+ main window, click Tuning - Tuning.
Click Cancel to return to the SigmaWin+ main window without executing tuning.
3.
Click Execute.
The following window will appear.
8.4 Advanced Autotuning by Reference
CAUTION
8
8-39