Write Prohibited Setting - YASKAWA E-V-MD Series User Manual

Ac, rotational motor, mechatrolink-iii communications references, servomotor
Table of Contents

Advertisement

(1) Preparation
There are no tasks that must be performed before the execution.
(2) Operating Procedure
Follow the steps to set enable or disable writing.
Setting values are as follows:
P.0000
: Write permitted (Releases write prohibited mode.) [Factory setting]
"
"
P.0001
: Write prohibited (Parameters become write prohibited from the next power ON.)
"
"
1.
In the SigmaWin+ main window, click Setup - Write Prohibited Setting.
The Write Prohibited Setting box will appear.
Set the parameter to enable or prohibit writing. Click the setting arrows to increase or decrease the num-
ber on the far right.
Writing enabled (factory setting): 0000
Writing prohibited: 0001
2.
Click Setting.
The following message appears and informs you that the write prohibited setting has been changed and
the new setting will become valid the next time the SERVOPACK is restarted.
3.
Click OK.
The new setting will be saved in the SERVOPACK.
4.
To enable the change in the setting, restart the SERVOPACK.

9.9 Write Prohibited Setting