Option: Deployment Profibus Communication; Fast Introduction - YASKAWA VIPA System SLIO Manual

Hide thumbs Also See for VIPA System SLIO:
Table of Contents

Advertisement

Option: Deployment PROFIBUS communication

Fast introduction

11
Option: Deployment PROFIBUS communication
11.1
Fast introduction
Overview
Steps of configuration
254
The PROFIBUS DP slave is to be configured in the hardware configurator from Siemens.
Here the configuration happens by the sub module X1 (MPI/DP) of the Siemens CPU.
To switch the interface X3 MPI(PtP) to PROFIBUS functionality you have
to activate the according bus functionality by means of a VSC storage
media from VIPA. By plugging the VSC storage card and then an overall
reset the according functionality is activated.
storage media - VSD, VSC' page 111
For the configuration of the PROFIBUS DP master please follow the following approach:
n
Enable bus functionality via VSC
Hardware configuration - CPU
n
Deployment as DP master or DP slave
n
With activating the bus function 'PROFIBUS DP master' by means of the VSC,
the bus function 'PROFIBUS DP slave' is also unlocked.
n
Transfer of the complete project to CPU
With the Siemens SIMATIC Manager, the CPU 013-CCF0R00 from VIPA
is to be configured as
CPU 314C-2 PN/DP (314-6EH04-0AB0 V3.3)
The integrated PROFIBUS DP master (X3) is to be configured and con-
nected via the sub module X1 (MPI/DP).
VIPA System SLIO
Ä Chap. 4.16 'Deployment
HB300 | CPU | 013-CCF0R00 | en | 19-30