YASKAWA VIPA System SLIO Manual page 165

Hide thumbs Also See for VIPA System SLIO:
Table of Contents

Advertisement

VIPA System SLIO
Record set 0
Diagnostic
incoming
HB300 | CPU | 013-CCF0R00 | en | 19-30
Byte
Bit 7...0
0
n
Bit 0: set at module failure
n
Bit 1: set at internal error
n
Bit 2: set at external error
n
Bit 3: set at channel error
n
Bit 4: set at missing external power supply
n
Bit 7 ... 5: 0 (fix)
1
n
Bit 3 ... 0: Module class
n
Bit 4: Channel information present
n
Bit 7 ... 5: 0 (fix)
2
n
Bit 3 ... 0: 0 (fix)
n
Bit 4: set at missing internal power supply
n
Bit 7 ... 5: 0 (fix)
3
n
Bit 5 ... 0: 0 (fix)
n
Bit 6: Process interrupt lost
n
Bit 7: 0 (fix)
Diagnostic and interrupt > Diagnostic interrupt
Counter/Frequency measurement: Process interrupt lost
Digital input: Process interrupt lost
Missing power supply DI or DO
Digital output: short circuit/overload
Output Sensor: short circuit/overload
SLIO bus: missing supply fieldbus
Diagnostic interrupt from SLIO modules
Missing power supply DI or DO
Digital output: short circuit/overload
Output Sensor: short circuit/overload
SLIO bus: missing supply fieldbus
SLIO bus: missing supply fieldbus
1111b: Digital module
or
1000b: Function module
Counter/Frequency measurement: Process interrupt lost
Digital input: Process interrupt lost
Missing power supply DI or DO
Digital output: short circuit/overload
Output Sensor: short circuit/overload
SLIO bus: missing supply fieldbus
Diagnostic interrupt from SLIO modules
Missing power supply DI or DO
Deployment I/O periphery
165