Hardware description
Structure > Interfaces
X1/X2: Ethernet PG/OP
channel
X3: MPI(PtP) interface
44
8pin RJ45 jack:
n
The RJ45 jack serves as interface to the Ethernet PG/OP channel.
n
This interface allows you to program respectively remote control your CPU and to
access the internal web server.
The Ethernet PG/OP channel (X1/X2) is designed as switch. This enables PG/OP
n
communication via the connections X1 and X2.
n
Configurable connections are possible.
n
DHCP respectively the assignment of the network configuration with a DHCP server
is supported.
n
Default diagnostics addresses: 2025 ... 2040
n
At the first commissioning respectively after a factory reset the Ethernet PG/OP
channel has no IP address. For online access to the CPU via the Ethernet PG/OP
channel, valid IP address parameters have to be assigned to this by means of your
configuration tool. This is called "initialization".
n
Via the Ethernet PG/OP channel, you have access to:
Device website, where you can find information on firmware status, connected
peripherals, current cycle times, etc.
OPC UA project, which is to be created in the OPC UA Configurator.
WebVisu project, which is to be created in the SPEED7 Studio.
PROFINET IO controller or the PROFINET I-Device.
Ä Chap. 4.7 'Hardware configuration - Ethernet PG/OP channel' page 72
Ä Chap. 9 'Deployment PG/OP communication - productive' page 214
9pin SubD jack: (isolated)
The interface supports the following functionalities, which are switch able:
n
MPI (default / after overall reset)
The MPI interface serves for the connection between programming unit and CPU. By
means of this the project engineering and programming happens. In addition MPI
serves for communication between several CPUs or between HMIs and CPU.
Standard setting is MPI address 2.
n
PtP
The RS485 interface can be switched to PtP functionality
specific CPU parameters' page 82. Using the PtP functionality the RS485 interface
is allowed to connect via serial point-to-point connection to different source res. target
systems.
The following protocols are supported:
ASCII
STX/ETX
3964R
USS
Modbus master (ASCII, RTU)
n
PROFIBUS DP (option)
The PROFIBUS functionality of this interface can be activated by configuring the sub
module X1 'MPI/DP' of the CPU in the hardware configuration.
Deployment PROFIBUS communication' page 254
To switch the interface X3 MPI(PtP) to PROFIBUS functionality you have
to activate the according bus functionality by means of a VSC storage
media from VIPA. By plugging the VSC storage card and then an overall
reset the according functionality is activated.
storage media - VSD, VSC' page 111
VIPA System SLIO
Ä Chap. 4.9 'Setting VIPA
Ä Chap. 11 'Option:
Ä Chap. 4.16 'Deployment
HB300 | CPU | 013-CCF0R00 | en | 19-30