Configuration with TIA Portal
TIA Portal - Hardware configuration - Ethernet PG/OP channel > Take IP address parameters in project
13.4.1.2
Configuration via additional CP
Proceeding
302
6.
Save and transfer your project to the CPU.
ð After transmission, the NTP time is requested by each configured time server
and the best response for the time synchronization is used.
Please note that although the time zone is evaluated, an automatic
changeover from winter to summer time is not supported. Industrial sys-
tems with time-of-day synchronization should always be set in accord-
ance to the winter time.
With the FC 61 you can determine the local time in the CPU. More infor-
mation about the usage of this block may be found in the manual
"SPEED7 Operation List" from VIPA.
This is the conventional variant for configuration and is supported by all firmware ver-
sions. If possible, always use the configuration via the internal interface, otherwise the fol-
lowing disadvantages result:
n
Address overlaps are not recognized in the Siemens TIA Portal.
n
For PROFINET devices only the address range 0 ... 1023 is available.
n
The addresses of the PROFINET devices are not checked with the address space of
the CPU from the Siemens TIA portal for address overlaps.
The configuration happens according to the following procedure:
1.
Open your project.
2.
If not already done, configure in the 'Device configuration' a Siemens CPU 314C-2
PN/DP (314-6EH04-0AB0 V3.3).
3.
As Ethernet PG/OP channel place at slot 4 the Siemens CP 343-1 (6GK7
343-1EX30 0XE0 V3.0).
CAUTION!
Please configure the diagnostic addresses of the CP343-1EX30 for
'PN-IO' , 'Port1' and 'Port2' so that no overlaps occur in the
periphery input area. Otherwise your CPU can not start-up and you
receive the diagnostic entry 0xE904. Address overlaps are not rec-
ognized in the Siemens TIA Portal.
4.
Open the 'Property' dialog by clicking on the CP 343-1EX30 and enter for the CP
at 'Properties' at 'Ethernet address' the IP address data and subnet, which you
have assigned before. The IP address data are not accepted without subnet assign-
ment!
5.
Transfer your project.
VIPA System SLIO
HB300 | CPU | 013-CCF0R00 | en | 19-30