Deployment PG/OP communication - PROFINET
Deployment as PROFINET I-Device > Configuration as I-Device
240
2.
Open the properties dialog of the PROFINET IO controller of the CPU by a double-
click at 'PN-IO' and assign the name for the I-Device.
Write down the Name. This name must also be specified as the
'device name' of the I-Device for the higher-level IO controller.
3.
For 'PN-IO' at 'slot' 'X...' assign an IP address via the properties dialog.
4.
Create the transfer areas by dragging them to the 'slots' as I/O areas from the
hardware catalog. There must be no gaps in the slots. To create the transfer areas,
the following input and output areas are available that can be assigned to the virtual
I-Device:
n
Input: 1, 8, 16, 32, 64, 128, 256, 512 byte
n
Output: 1, 8, 16, 32, 64, 128, 256, 512 byte
The data direction for Input or Output refers to the view of the I-Device.
Input areas define data that are sent from the higher-level IO controller to the I-
n
Device and which are mapped to the input address area of the CPU.
n
Output areas define data that are sent to the higher-level IO controller and
which are to stored in the output address area of the CPU.
5.
Save and transfer your project to the CPU.
VIPA System SLIO
HB300 | CPU | 013-CCF0R00 | en | 19-30