Configuration of the slave
part
13.8

Deployment OPC UA

HB300 | CPU | 013-CCF0R00 | en | 19-30
1.
Configure a Siemens CPU 314C-2 PN/DP (314-6EH04-0AB0 V3.3) as another CPU
Ä Chap. 13.3 'TIA Portal - Hardware configuration - CPU' page 296
2.
Designate the station as "... DP slave".
3.
Integrate your modules according to your hardware configuration.
4.
Select the PROFIBUS interface of your CPU and select 'Context menu
è Properties'.
ð The 'Properties' dialog is shown.
5.
Set at interface: Type "PROFIBUS".
6.
Connect to PROFIBUS and preset an address (e.g. 3).
7.
Switch at 'Operating mode' to "DP slave".
8.
Under 'Assigned DP master' , select your master system.
9.
Use 'Transfer area' to define the I/O address areas of the slave CPU that are to be
assigned to the DP slave.
10.
Save, translate and transfer the respective project into the corresponding master or
slave CPU.
Ä Chap. 7 'Deployment OPC UA' page 183
Configuration with TIA Portal
Deployment OPC UA
319