11.5

Deployment as PROFIBUS DP master

Precondition
Proceeding
HB300 | CPU | 013-CCF0R00 | en | 19-30
The hardware configuration described before was established.
1.
Open the properties dialog of the DP interface of the CPU by means of a double-
click at 'MPI/DP' .
2.
Set at Interface: Type "PROFIBUS".
3.
Connect to PROFIBUS and preset an address (preferably 2). Confirm your input
with [OK].
4.
Switch at Operating mode to "DP master" and confirm the dialog with [OK].
ð A PROFIBUS DP master system is inserted:
Now the project engineering of your PROFIBUS DP master is finished. Please link up
now your DP slaves with periphery to your DP master.
1.
For the project engineering of PROFIBUS DP slaves you search the concerning
PROFIBUS DP slave in the hardware catalog and drag&drop it in the subnet of your
master.
2.
Assign a valid PROFIBUS address to the DP slave.
3.
Link up the modules of your DP slave system in the plugged sequence and add the
addresses that should be used by the modules.
4.
If needed, parametrize the modules.
5.
Save, compile and transfer your project.
Option: Deployment PROFIBUS communication
Deployment as PROFIBUS DP master