YASKAWA VIPA System SLIO Manual page 369

Hide thumbs Also See for VIPA System SLIO:
Table of Contents

Advertisement

VIPA System SLIO
Event ID
HB300 | CPU | 013-CCF0R00 | en | 19-30
Description
3: Bootstrap
4: SafeOp
8: Op
ZINFO1 - Position 8: Previous status
0: Undefined/Unkown
1: Init
2: PreOp
3: Bootstrap
4: SafeOp
8: Op
ZINFO2: Diagnostic address of the station
ZINFO3: AlStatusCode
0: No error
1: Unspecified error
17: Invalid requested status change
18: Unknown requested status
19: Bootstrap not supported
20: No valid firmware
22: Invalid mailbox configuration
23: Invalid sync manager configuration
24: No valid inputs available
25: No valid outputs available
26: Synchronisation error
27: Sync manager watchdog
28: Invalid sync manager types
29: Invalid output configuration
30: Invalid input configuration
31: Invalid watchdog configuration
32: Slave station needs cold start
33: Slave station needs to be in INIT state
34: Slave station needs to be in PreOp state
35: Slave station needs to be in SafeOp state
45: Invalid output FMMU configuration
46: Invalid input FMMU configuration
48: Invalid DC Sync configuration
49: Invalid DC Latch configuration
50: PLL error
51: Invalid DC IO error
System specific event IDs
369

Advertisement

Table of Contents
loading

Table of Contents