Deployment CPU 013-CCF0R00
Accessing the web server > Device web page CPU
Start Conditions
Server
4.11.1.1.2
Tab: 'WebVisu'
98
Here the start conditions for the OPC UA server are listed:
n
Conflicting projects
Simultaneous use of an OPC UA and WebVisu project via the same interface is
not permitted and results in the message 'conflicting project on card' .
The status 'no conflicting project on card' indicates that there is no conflict with a
WebVisu project on the same interface.
n
Feature Set activated
yes: The OPC UA functionality is activated.
no: The OPC UA functionality is not activated.
Ä Chap. 7.3 'Activate OPC UA functionality' page 192
n
Allowed by User
yes: The OPC UA server is activated and access to it is allowed. As soon as an
OPC UA project is found on the memory card, it is automatically started and ena-
bled for access.
no: You can disable and stop the OPC UA server by means of the CMD - auto
command 'OPCUA_PGOP_DISABLE' . With 'OPCUA_PGOP_ENABLE' you can
enable to restart the OPC UA server.
Ä Chap. 4.18 'CMD - auto commands' page 114
n
Allowed by Access Ways
yes: By default, the OPC UA protocol is enabled.
no: The OPC UA protocol is disabled. You can deactivate or activate the OPC UA
protocol by means of the parameter 'OPC UA' in the 'Access settings' .
Hardware configured
n
yes: A hardware configuration as a precondition for the OPC UA communication
is loaded. The hardware configuration is checked for validity elsewhere.
no: A hardware configuration is not loaded e.g. after an overall reset.
Ä Chap. 4.5 'Hardware configuration - CPU' page 69
OPC UA project
n
loaded: An OPC UAOPC UA project is loaded.
not loaded: An OPC UAOPC UA project is not loaded.
Ä Chap. 7 'Deployment OPC UA' page 183
n
State
Running: The start conditions are fulfilled and the OPC UA server is started.
Stopped: The OPC UA server is stopped.
Startup failure: The OPC UA server can not be started.
Starting: The OPC UA server currently starts up.
Stopping: The OPC UA server currently stopps.
n
Endpoint URL
As soon as the OPC UA server is started, the endpoint URL of the OPC UA
server is listed here.
Information about the web visualization ( 'WebVisu' ) are shown here. The creation of a
'WebVisu' project is only possible with the SPEED7 Studio V1.7.0 and up.
'Deployment WebVisu - Web visualization' page 209