Deployment CPU 013-CCF0R00
Accessing the web server > Device web page CPU
Status of the WebVisu
Status
running
loading webvisu project
shutting down
stop requested
stopped
webvisu feature not activated
webvisu is disabled by the user
no webvisu project file found
no hardware configuration loaded
invalid configuration
internal error: filesystem
webvisu project file too large
loading webvisu project file
deleting webvisu project
internal error: file system - delete
CRC mismatch
webvisu stopped
internal error 1
internal error 2
internal error 3
unknown error
4.11.1.1.3
Tab: 'Port Mirroring'
Overview
Enable Port Mirroring
100
On the device web page at the tab 'WebVisu' via 'Status' you get the status of your
WebVisu project.
Meaning
WebVisu is active / has started-up and can be opened
Loading WebVisu project
WebVisu server shuts down
WebVisu STOP requested
WebVisu server is down
WebVisu not activated, memory card is not inserted
WebVisu was disabled by the user
No WebVisu project found
No hardware configuration is loaded
Invalid WebVisu configuration
Error initializing the file system
Error loading WebVisu project, project file too large
Error loading WebVisu project, project file may be damaged
Failed to delete the WebVisu project
WebVisu project to be deleted was not found in the memory
CRC of the WebVisu project file is not correct
WebVisu server has terminated unexpectedly
Internal error - initialization failed step 1
Internal error - initialization failed step 2
Unexpected internal error
General error
n
Port Mirroring offers the possibility to diagnose the communication without additional
hardware effort.
n
The Ethernet PG/OP interface is designed as switch.
n
When Port Mirroring of the PG/OP2: X2 (Mirror Port) interface is activated, all tele-
grams received and sent via the PG/OP1: X1 interface are mirrored to the PG/OP2:
X2 interface and vice versa.
n
When Port Mirroring is activated, for diagnostics with diagnostics software such as
Wireshark, you can connect your PC directly to the 2. interface.
n
The next power-cycle will automatically disable Port Mirroring.
When enabled, you can set the parameters for Port Mirroring.