VIPA System SLIO
5.6.2.2
Counter outputs
X5: Connector
X5
Function
1
Sys DC 24V
2
Sys 0V
6
DO 0
7
DO 1
8
DO 2
9
DO 3
18
DC 24V
19
0 V
20
DC 24V
21
0 V
Output channel Counter
HB300 | CPU | 013-CCF0R00 | en | 19-30
For not all inputs are available at the same time, for every counter you may define the
input assignment via the parameterization for the following input signals:
n
Counter
(A)
x
Pulse input for counter signal respectively track A of an encoder for 1-, 2- or 4-fold
evaluation.
n
Counter
(B)
x
Direction signal respectively track B of the encoder. Via the parameterization you
may invert the direction signal.
n
Gate 3
Via this input you can if parameterized open the HW gate of Counter 3 with edge
0-1 and start counting.
n
Latch 3
Via this input via edge 0-1 the current counter value of Counter 3 is stored in a
memory that you may read if needed.
Type
Description
I
1L+: DC 24V for electronic section supply
I
1M: GND for electronic section supply
O
+0.0: Output channel counter 0
O
+0.1: Output channel counter 1
O
+0.2: Output channel counter 2
O
+0.3: Output channel counter 3
I
2L+: DC 24V power section supply for on-board counter
I
2M: GND power section supply for on-board counter
I
3L+: DC 24V SLIO bus power section supply
I
3M: GND SLIO bus power section supply
Every counter has an assigned output channel. For each counter you can specify the
x
behavior of the counter output via the parametrization with 'Characteristics of the output'
and 'Pulse duration' .
Ä Chap. 5.6.4.3 'Counter' page 131
Deployment I/O periphery
Counting > Wiring
129