Voltage measurement
0 ... 10V
Measuring range
Voltage
(U)
0 ... 10V
> 11.759V
11.759V
10V
5V
0V
-0.8V
< -0.8V

5.3.3 Wiring

X4: Connector
X4
Function
1
AI 0
2
AI 1
3
Analog 0V
Cables for analog signals
HB300 | CPU | 013-CCF0R00 | en | 19-30
Decimal
(D)
32767
32511
27648
13824
0
-2212
-32768
Type
Description
I
AI0: Analog input AI 0
I
AI1: Analog input AI 1
I
4M: GND for analog inputs
For the analog signals you have to use isolated cables. With this the interferences can be
reduced. The shield of the analog cables should be grounded at both ends. If there are
potential differences between the cables, a potential compensation current can flow,
which could disturb the analog signals. In this case, you should only ground the shield at
one end of the cable.
Temporarily not used analog inputs must be connected to the concerning
ground.
Hex
Range
7FFFh
overflow
7EFFh
overdrive range
6C00h
nominal range
3600h
0000h
F75Ch
underdrive range
8000h
underflow
Deployment I/O periphery
Analog input > Wiring
Formulas
D: decimal value
U: voltage value
121