Configuration with VIPA SPEED7 Studio
Deployment I/O periphery > Frequency measurement
Sub module
Output address
Count
816
820
824
828
12.6.6.2.2
Basic parameters
Select interrupt
12.6.6.2.3
'Channel x:'
Operating mode
Parameter overview
Operating parameters
Integration time
max. counting frequency ...
284
Access
DWORD
DWORD
DWORD
DWORD
Via 'Basic parameters' you can reach 'Select interrupt' . Here you can define the inter-
rupts the CPU will trigger. The following parameters are supported:
n
None: The interrupt function is disabled.
n
Process: The following events of the frequency measurement can trigger a hardware
interrupt (selectable via 'Frequency counting' ):
End of measurement
n
Diagnostics+process: A diagnostics interrupt is only triggered when a hardware inter-
rupt was lost.
Select via 'Channel' the channel and select for frequency measurement via 'Operating
mode' the operating mode 'Frequency counting' . Default values and structure of this
dialog box depend on the selected 'Operating mode' . The following parameters are sup-
ported:
1
Integration time
2
Counting pulse
3
SW gate
4
Evaluated frequency
Description
Specify the integration time
Range of values: 10ms ... 10000ms in steps of 1ms
Specify the max. frequency for the corresponding input
Frequency
shortest permissible count pulse
1kHz
400µs
2kHz
200µs
5kHz
80µs
Assignment
reserved
reserved
reserved
reserved
HB300 | CPU | 013-CCF0R00 | en | 19-30
VIPA System SLIO
Assignment
100ms
60kHz