YASKAWA VIPA System SLIO Manual page 286

Hide thumbs Also See for VIPA System SLIO:
Table of Contents

Advertisement

Configuration with VIPA SPEED7 Studio
Deployment I/O periphery > Pulse width modulation - PWM
Parameter overview
Operating parameters
Output format
Time base
On-delay
286
1
Period
2
On-delay
3
Pulse duration
4
Pulse pause
Description
Here specify the range of values for the output. The CPU
hereby determines the pulse duration:
Per mil
n
Output value is within 0 ... 1000
Pulse duration = (Output value / 1000) x Period
n
S7 Analog value:
Output value is Siemens S7 analog value 0 ...
27648
Pulse duration = (Output value / 27648) x Period
Here you can set the time base, which will apply for resolu-
tion and range of values of the period duration, minimum
pulse duration and on-delay.
1ms: The time base is 1ms
n
0.1ms: The time base is 0.1ms
n
n
1µs: The time base is 1µs
Enter here a value for the time to expire from the start of
the output sequence to the output of the pulse. The pulse
sequence is output at the output channel, on expiration of
the on-delay.
Range of values: 0 ... 65535 from this there are the fol-
lowing effective values:
n
Time base 1ms: 0 ... 65535ms
n
Time base 0.1ms: 0 ... 6553.5ms
n
Time base 1µs: 0 ... 65535µs
VIPA System SLIO
Assignment
Per mil
0.1ms
0
HB300 | CPU | 013-CCF0R00 | en | 19-30