4.7.1.2.1
Time-of-day synchronization
NTP method
HB300 | CPU | 013-CCF0R00 | en | 19-30
Hardware configuration - Ethernet PG/OP channel > Take IP address parameters in project
In the NTP mode (Network Time Protocol) the module sends as client time-of-day queries
at regular intervals to all configured NTP servers within the sub net. You can define up to
4 NTP server. Based on the response from the servers, the most reliable and most exact
time-of-day is determined. Here the time with the lowest stratum is used. Stratum 0 is the
time standard (atomic clock). Stratum 1 are directly linked to this NTP server. Using the
NTP method, clocks can be synchronized over subnet boundaries. The configuration of
the NTP servers is carried out in the Siemens SIMATIC Manager via the CP, which is
already configured.
1.
Open the properties dialog via double-click on the CP 343-1EX30.
2.
Select the register 'Time-of-day synchronization' .
3.
Activate the NTP method by enabling 'Activate NTP time-of-day synchronization' .
4.
Click at [Add] and add the corresponding NTP server.
5.
Select your 'time zone' . In the NTP method, UTC (Universal Time Coordinated) is
generally transmitted; this corresponds to GMT (Greenwich Mean Time). By config-
uring the local time zone, you can set a time offset to UTC.
6.
Select your 'Update interval' . Within this interval the time of the module is
synchronized once.
7.
Close the dialog with [OK].
8.
Save and transfer your project to the CPU.
ð After transmission, the NTP time is requested by each configured time server
and the best response for the time synchronization is used.
Please note that although the time zone is evaluated, an automatic
changeover from winter to summer time is not supported. Industrial sys-
tems with time-of-day synchronization should always be set in accord-
ance to the winter time.
The FC 61 can be used to determine the local time in the CPU. More
information about the usage of this block may be found in the manual
"SPEED7 Operation List" from VIPA.