Deployment I/O periphery
Analog input > Parametrization

5.3.4 Parametrization

5.3.4.1
Adress assignment
Sub module
Input
address
AI5/AO2
800
802
5.3.4.2
Filter
Parameter hardware con-
figuration
Parametrization during
runtime
Record set 1
Byte
Bit 7 ... Bit 0
0
Bit 7...0: reserved
1
Filter
n
Bit 1, 0: Analog input channel 0
Bit 3, 2: Analog input channel 1
00b: 'Integration time 2.5ms' ≙ 2ms (no filter)
01b: 'Integration time 16.6ms' ≙ 100ms (small filter)
10b: 'Integration time 20ms' ≙ 1000ms (medium filter)
n
Bit 7...4: reserved
2...12
Bit 7...0: reserved
122
Access
Description
WORD
Analog input channel 0 (X4)
WORD
Analog input channel 1 (X4)
The analog input part has a filter integrated. The parametrization of the filter happens in
the Siemens SIMATIC Manager via the parameter 'Integration time' . The default value of
the filter is 1000ms. The following values can be entered:
≙ Channel 0'
n
'Input 0
≙ Channel 1'
'Input 1
'Integration time 2.5ms' ≙ 2ms (no filter)
'Integration time 16.6ms' ≙ 100ms (small filter)
'Integration time 20ms' ≙1000ms (medium filter)
By using the record set 1 of the SFC 55 "WR_PARM" you may alter the parametrization
in the module during runtime.
The time needed until the new parametrization is valid can last up to 2ms.
During this time, the measuring value output is 7FFFFh.
VIPA System SLIO
Default
00h
10h
HB300 | CPU | 013-CCF0R00 | en | 19-30