Wiring; Proceeding - YASKAWA VIPA System SLIO Manual

Hide thumbs Also See for VIPA System SLIO:
Table of Contents

Advertisement

Deployment I/O periphery
Pulse train > Proceeding

5.9.2 Wiring

5.9.2.1
Pulse train outputs
X5: Connector
X5
Function
1
Sys DC 24V
2
Sys 0V
6
DO 0.0
7
DO 0.1
18
DC 24V
19
0V
20
DC 24V
21
0V

5.9.3 Proceeding

Hardware configuration
158
Type
Description
I
1L+ DC 24V for electronic section supply
I
1M: GND for electronic section supply
O
Pulse train 0
O
Pulse train 1
I
2L+ 24V DC power section supply for pulse train
I
2M: GND for pulse train
I
3L+: DC 24V SLIO bus power section supply
I
3M: GND SLIO bus power section supply
PWM and pulse train output use the same hardware configuration. Switching between
these modes is done within SFB 49. In the Siemens SIMATIC Manager the following
steps should be executed:
1.
Perform a hardware configuration for the CPU.
tion - CPU' page 69
2.
Double-click the counter sub module of the CPU 314C-2 PN/DP.
ð The dialog 'Properties' is opened.
3.
As soon as you select the operating mode for the corresponding channel, a dialog
box with default values for this counter mode is created and shown. For PWM
respectively pulse train output select for the corresponding channel the operating
mode 'Pulse width modulation - PWM' .
4.
Perform the required parameter settings.
5.
Safe your project with 'Station è Safe and compile'.
6.
Transfer your project to your CPU.
VIPA System SLIO
Ä Chap. 4.5 'Hardware configura-
HB300 | CPU | 013-CCF0R00 | en | 19-30