TIA Portal - Deployment PG/OP communication - PROFINET > Deployment as PROFINET I-Device
2.
For the project engineering of the VIPA I-Device in the high-level IO controller you
have to search the device 'PN I-Device config for higher-level CPU' in the hardware
catalog at PROFINET-IO drag it to Network view and connect it via PROFINET to
the CPU.
3.
In the 'Network view' , click on the 'PN-I-Device' and enter at 'Device name' the
previously noted name of the VIPA I-Device.
The configured name must match the name of the CP 343-1 inter-
face of the I-Device CPU, which you have written down before!
Ä Chap. 13.6.2.3 'Configuration as I-Device' page 312
4.
Configure an input area of the same size for each output area of the I-Device in the
IO controller and vice versa. Here also no gaps may arise. In particular, make sure
that the order of the transfer areas matches that of the I-Device configuration. The
following transfer units are available:
n
Input: 1, 8, 16, 32, 64, 128, 256, 512 byte per slot
n
Output: 1, 8, 16, 32, 64, 128, 256, 512 byte per slot
5.
Save and transfer your project to the CPU.
ð Your VIPA PROFINET controller is now connected as an I-Device to the higher-
level PROFINET IO controller.
Configuration with TIA Portal