VIPA System SLIO
5.6.5.2.2
Main counting direction forward
HB300 | CPU | 013-CCF0R00 | en | 19-30
n
The counter counts forward starting with the load value.
n
When the counter reaches the End value -1 in positive direction, it jumps to the load
value at the next count pulse and the gate is automatically closed.
n
To restart the count process, you have to generate an edge 0-1 at the gate
5.6.6.2 'Gate function' page 142. The counter counts starting with the load value.
n
You may exceed the lower count limit.
Limits
End value
Lower count limit
Counting > Counter operating modes
Valid range of values
-2 147 483 647 (-2
31
+1)
up to +2 147 483 647 (2
-2 147 483 648 (-2
31
)
Deployment I/O periphery
Ä Chap.
31
-1)
137