YASKAWA VIPA System SLIO Manual page 23

Hide thumbs Also See for VIPA System SLIO:
Table of Contents

Advertisement

VIPA System SLIO
Wiring procedure
Insert wire
Remove wire
Remove connectors
(module replacement)
HB300 | CPU | 013-CCF0R00 | en | 19-30
1
Labeling on the casing
2
Pin no. at the connector
3
Release button
4
Connection hole for wire
The wiring happens without a tool.
Determine according to the casing labelling the connection position and insert
through the round connection hole of the according contact your prepared wire until
it stops, so that it is fixed.
ð By pushing the contact spring opens, thus ensuring the necessary contact pres-
sure.
The wire is to be removed by means of a screwdriver with 2.5mm blade width.
1.
Press with your screwdriver vertically at the release button.
ð The contact spring releases the wire.
2.
Pull the wire from the round hole.
By means of a screwdriver there is the possibility to remove the connectors e.g. for
module exchange with a fix wiring. For this each connector has a release lever centrally
on its top side. Unlocking takes place by the following proceeding:
1.
Remove connector:
Push your screwdriver horizontally into the slot between connector and release
lever, until it stops.
2.
Push the screwdriver down:
ð The connector is unlocked and can be removed by turning downwards.
CAUTION!
Via wrong operation such as pressing, the screwdriver upward
the release lever may be damaged.
3.
Plug connector:
The connector is plugged by setting it at the bottom line and engage with a with a
slight twist upwards into the release lever.
Basics and mounting
Wiring > Wiring CPU 01xC
23