Configuration with TIA Portal
TIA Portal - Deployment PG/OP communication - PROFINET > Deployment as PROFINET I-Device
13.6.2.4
Configuration in the higher-level IO controller
314
7.
Create the transfer areas by dragging them to the 'Slots' as I/O areas from the
hardware catalog to the Device view. There must be no gaps in the slots. To create
the transfer areas, the following input and output areas are available that can be
assigned to the virtual I-Device:
n
Input: 1, 8, 16, 32, 64, 128, 256, 512 byte
n
Output: 1, 8, 16, 32, 64, 128, 256, 512 byte
The data direction for Input or Output refers to the view of the I-Device.
Input areas define data that are sent from the higher-level IO controller to the I-
n
Device and which are mapped to the input address area of the CPU.
n
Output areas define data that are sent to the higher-level IO controller and
which are to stored in the output address area of the CPU.
8.
Save and transfer your project to the CPU.
It is assumed that a CPU is configured with IP address with the higher-level IO controller.
The IP address must be in the same IP circuit as the IP address of the I-Device.
1.
Open the project of the CPU with the higher-level IO controller.