Deployment PG/OP communication - PROFINET
Deployment as PROFINET I-Device > Error behavior and interrupts
Starting position
Event
Reaction
244
IO controller is in STOP, I-Device in RUN
IO controller starts
n
The OB 83 (Return-of-Submodule) for input sub modules of the transfer
areas to the higher-level IO controller is called in the I-Device.
n
An OB 85 is called for each transfer area, which is located in the process
image, in the I-device if messages of process image transfer errors are par-
ametrized and the corresponding OB 83 has not yet been called.
n
An OB 122 is triggered in the I-Device for each peripheral direct access to
an input transfer area, until the corresponding OB 83 has been called.
n
The OB 100 (startup) is called in the IO controller.