4.17 Instructions for commissioning induction motors (ASM)

4.17
Instructions for commissioning induction motors (ASM)
Equivalent circuit diagram for induction motor and cable
Figure 4-23
Equivalent circuit diagram for induction motor and cable
Induction motors, rotating
The following parameters must be entered in the commissioning wizard of STARTER:
Table 4- 3
Motor data type plate
Parameter
Description
p0304
Rated motor voltage
p0305
Rated motor current
p0307
Rated motor power
p0308
Rated motor power factor
p0310
Rated motor frequency
p0311
Motor rated speed
p0335
Motor cooling type
The following parameters can be optionally entered:
216
Remark
If this value is not known, a "0" can also be
entered. Using this value, the stator leakage
inductance can be more precisely calculated
(p0356, p0357).
-
-
-
-
-
-