3.9 V/f control
Requirements for V/f control
● First commissioning has been carried out:
● First commissioning has not been carried out:
Note
With synchronous motors, V/f mode is normally only stable at low speeds. Higher speeds
can induce vibrations.
Oscillation damping is activated on the basis of suitable default parameter values and does
not require further parameterization in most applications. If you become aware of
interference caused by a transient response, you have the option of gradually increasing the
value of p1338 and evaluating how this affects your system.
Note
The drive can be ramped up to the current limit (p0640) relatively quickly without the need for
extensive parameterization (when operating the drive with a variable moment of inertia, for
example).
Note the following: Only the ramp-function generator stops when the current limit (p0640) is
reached. This does not prevent the current from increasing even further. In view of this, the
parameters you set must include a safety margin relative to the current limits for the
monitoring functions to prevent the drive from switching off with an overcurrent fault.
110
The parameters for V/f control have been initialized with appropriate values.
The following relevant motor data must be checked and corrected:
– r0313 Motor pole pair number, actual (or calculated)
– p0314 Motor pole pair number
– p1318 V/f control ramp-up/ramp-down time
– p1319 V/f control voltage at zero frequency
– p1326 V/f control programmable characteristic frequency 4
– p1327 V/f control programmable characteristic voltage 4
– p1338[0...n] V/f mode resonance damping gain
– p1339[0...n] V/f mode resonance damping filter time constant
– p1349[0...n] V/f mode resonance damping maximum frequency
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3