6.11.3

Configuring the fault response

Changing the fault response
The responses can be set to selected faults using parameters p2100 and p2101. Only
responses can be set that are intended for the corresponding faults.
Using parameter p0491, responses to encoder errors of a motor encoder can be set (F07412
and many F3yxxx, y = 1, 2, 3).
Note
Motor type change
If the preconditions for armature short-circuit braking or DC braking are no longer satisfied
after a motor type has been changed (see p0300), then those modified parameters that have
armature short-circuit braking or DC braking as a response (e.g. p2100, p2101 or p0491) are
set to the factory setting.
Note
Deselecting armature short-circuit or DC braking
Armature short-circuit or DC braking cannot be deactivated using parameter p1231, as long
as a response parameterized with p2100, p2101 or p0491 has a fault condition.
6.11.4

Function diagrams and parameters

Function diagrams (see SINAMICS S120/S150 List Manual)
• 7014
• 7016
• 7017
Drive functions
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
Technology functions - External armature short circuit
(EASC, p0300 = 2xx or 4xx)
Technology functions - Internal armature short-circuit
(IVP, p0300 = 2xx or 4xx)
Technology functions - DC braking (p0300 = 1xx)
6.11 Armature short-circuit braking, DC braking
Basic functions
299