Terminal Module 31 - Siemens SINAMICS S120 Function Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Monitoring and protective functions
8.5 Thermal motor protection
Table 8- 5
Device
TM31
TM120
TM150
) You will find more detailed information on sensor connections in the section on TM 150
1
8.5.5

Terminal Module 31

A Terminal Module 31 (TM31) is used when additional digital and analog inputs/outputs
required. The temperature sensor is connected at terminal X522. The values of the fault
and/or alarm thresholds can be set in parameter p4102[0..1] from -48 °C to 251 °C.
p4102 = 251°C deactivates the alarm and fault threshold. The factory setting is 100 °C for
the alarm threshold and 120 °C for the fault threshold.
Temperature measurement
● p0600 = 10 activates the motor temperature measurement via the external sensor.
● p0603 sets the signal source for the evaluation of the motor temperature
● p4100 = 0 disables the evaluation. Then parameter r4105 = -300°C.
544
Temperature sensor connection
Interface
Channel
X522
0
X521
0
1
2
3
X531
0
1)
X532
1
1)
X533
2
1)
X534
3
1)
X535
4
1)
X536
5
1)
+Temp -Temp
Temperature sensor type
7
8
KTY84 / PTC
2
1
KTY84-1C130/PTC/bimetallic NC contact,
linear motor: KTY84-1C130
4
3
KTY84-1C130/PTC/bimetallic NC contact,
linear motor: KTY84-1C130
6
5
KTY84-1C130/PTC/bimetallic NC contact,
linear motor: KTY84-1C130
8
7
KTY84-1C130/PTC/bimetallic NC contact,
linear motor: KTY84-1C130
1
2
KTY84-1C130/PTC/bimetallic NC
3
4
contact/PT100/PT1000
1
2
KTY84-1C130/PTC/bimetallic NC
3
4
contact/PT100/PT1000
1
2
KTY84-1C130/PTC/bimetallic NC
3
4
contact/PT100/PT1000
1
2
KTY84-1C130/PTC/bimetallic NC
3
4
contact/PT100/PT1000
1
2
KTY84-1C130/PTC/bimetallic NC
3
4
contact/PT100/PT1000
1
2
KTY84-1C130/PTC/bimetallic NC
3
4
contact/PT100/PT1000
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3