Sensor monitoring for wire breakage/short-circuit
● A sensor monitoring function for a short-circuit in the sensor cable is possible for a PTC
● If an induction motor is connected, you can suppress fault F07016 by setting p0607 = 0.
● If the motor temperature sensor set in p0600 is not connected, alarm A07820
8.5.12

Function diagrams and parameters

Function diagrams (see SINAMICS S120/S150 List Manual)
• 8016
• 8017
• 9576
• 9605
• 9606
• 9625
• 9626
• 9627
Drive functions
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
and a KTY84 . Wire break monitoring is possible for a KTY84 sensor:
If the temperature value lies outside the specified range of -140 °C ... +250 °C, then it is
probable that the sensor cable either has a broken wire or short-circuit. The alarm
A07015 "Drive: Motor temperature sensor alarm" is initiated. After the wait time in p0607
has expired, fault F07016 "Drive: Motor temperature sensor fault" is output.
The drive then continues to operate with the data calculated in the thermal 3-mass model.
"Temperature sensor not connected" is triggered.
Signals and monitoring functions - Thermal monitoring motor
Signals and monitoring functions - Thermal motor models
Terminal Module 31 (TM31) - Temperature evaluation (KTY/PTC)
Terminal Module 120 (TM120) - Temperature evaluation, channels 0 and 1
(KTY/PTC/bimetallic switch)
Terminal Module 120 (TM120) - Temperature evaluation, channels 2 and 3
(KTY/PTC/bimetallic switch)
Terminal Module 150 (TM150) - Temperature evaluation structure
(channel 0 ... 11)
Terminal Module 150 (TM150) - Temperature evaluation 1x2-, 3-, 4-wire
(channel 0 ... 5)
Terminal Module 150 (TM150) - Temperature evaluation 2x2-wire
(channel 0 ... 11)
Monitoring and protective functions
8.5 Thermal motor protection