Current Controller Adaptation - Siemens SINAMICS S120 Function Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

4.13

Current controller adaptation

Current controller adaptation can be used to adapt the P gain of the current controller and
the dynamic precontrol of the Iq current controller depending on the current. The current
controller adaptation is directly activated with setting p1402.2 = 1 or deactivated with
p1402.2 = 0. It is automatically activated with p1959.5 (p1959.5 = 1) or deactivated (p1959.5
= 0).
Figure 4-17
When swapping the iq interpolation points (e.g. for ASM), the current controller adaptation
appears as follows:
Figure 4-18
Function diagrams (see SINAMICS S120/S150 List Manual)
• 6710
• 6714
Drive functions
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
Current controller adaptation for p0393 < 1, with p0391 < p0392
Kp
p1715 x p0393
p1715
p0392
Current controller adaptation with swapped iq interpolation points for p0393 > 1, with
p0392 < p0391
Vector control - Current setpoint filter
Vector control - Iq and Id controller
4.13 Current controller adaptation
Iq
p0391
Vector control
201