Example
The following parameters must be set after the bypass function with synchronization with
overlap (p1260 = 1) has been activated.
Table 4- 9
Parameter
r1261.0 =
r1261.1 =
p1266 =
p1267.0 = 1
p1267.1 = 0
P1269[0] =
P1269[1] =
p3800 = 1
p3802 = r1261.2
Figure 4-29
Signal diagram, bypass with synchronization with overlap
Drive functions
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
Parameter setting for bypass function with synchronization with overlap
Description
Control signal for contactor K1
Control signal for contactor K2
Control signal setting when p1267.0 = 1
Bypass function is initiated by the control signal
Signal source to provide the feedback signal of contactor K1
Signal source for contactor K2 feedback
For synchronization, the internal voltages are used.
Synchronizer activation is triggered by the bypass function.
Vector control
4.25 Bypass
243