If a signal at binector input p2613 (reversing cam, MINUS) or at binector input p2614
(reversing cam, PLUS) is detected during reference point approach, the search direction is
reversed.
If the minus reversing cam is approached in the positive direction of travel or the plus
reversing cam in the negative direction of travel, fault F07499 (EPOS: reversing cam
approached with the incorrect traversing direction) is output. In this case, the wiring of the
reversing cams (BI: p2613, BI: p2614) or the direction of approach to the reversing cam must
be checked.
The reversing cams are low active. If both reversing cams are active (p2613 = "0" and p2614
= "0"), the drive remains stationary. As soon as the reference cam is found, then
synchronization to the reference zero mark is immediately started (refer to step 2).
If the axis leaves its start position and travels the distance defined in parameter p2606 (max.
distance to reference cam) heading towards the reference cam without actually reaching the
reference cam, the drive remains stationary and fault F07458 (reference cam not found) is
issued.
If the axis is already located at the cam, when referencing is started, then traversing to the
reference cam is not executed, but synchronization to the reference zero mark is
immediately started (refer to step 2).
Note
The velocity override is effective during the search for the cam. By changing the encoder
data set, status signal r2684.11 (reference point set) is reset.
The cam switch must be able to supply both a rising and a falling edge. For a reference point
approach with evaluation of the encoder zero mark, for increasing actual position values the
0/1 edge is evaluated and for decreasing actual position values, the 1/0 edge. Inversion of
the edge evaluation is not possible at the sensor zero mark.
If the length measuring system has several zero marks which repeat at cyclic intervals (e.g.
incremental, rotary measuring system), you must ensure that the cam is adjusted so that the
same zero mark is always evaluated.
The following factors may impact the behavior of the "reference cam" control signal:
• Switching accuracy and time delay of reference cam switch
• Position controller cycle of drive
• Interpolation cycle of drive
• Temperature sensitivity of machine's mechanical system
Drive functions
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
Function modules
7.8 Basic positioner