Servo control
3.11 Sensorless operation (without an encoder)
To accept a high load torque even in the open-loop controlled range, the motor current can
be increased via p1612. To do so, the drive torque (e.g. friction torque) must be known or
estimated. An additional reserve of approx. 20% should also be added. In synchronous
motors, the torque is converted to the current via the motor torque constant (p0316). In the
lower speed range, the required current cannot be measured directly on the Motor Module.
The default setting is 50% (synchronous motor) or 80% (induction motor) of the motor rated
current (p0305). When parameterizing the motor current (p1612), you must take into account
the thermal motor load.
Note
Encoderless operation is not permitted for vertical axes or similar. Encoderless operation is
not suitable for a higher-level closed-loop position control either.
The start behavior of synchronous motors from standstill can be improved further by
parameterizing the pole position identification (p1982 = 1).
Behavior once pulses have been canceled
Once the pulses have been canceled in operation without an encoder, the current actual
speed value of the motor can no longer be calculated. Once the pulses are enabled again,
the system must search for the actual speed value.
p1400.11 can be used to parameterize whether the search is to begin with the speed
setpoint (p1400.11 = 1) or with speed = 0.0 (p1400.11 = 0). Under normal circumstances,
p1400.11 = 0 because the motor is usually started from standstill. If the motor is rotating
faster than the changeover speed p1755 when the pulses are enabled, p1400.11 = 1 must
be set.
If the motor is rotating and the start value for the search is as of the setpoint (p1400.11 = 1),
the speed setpoint must be in the same direction as the actual speed before the pulses can
be enabled. A large discrepancy between the actual and setpoint speed can cause a
malfunction.
NOTICE
Missing information about the motor speed
Once the pulses have been canceled, no information about the motor speed is available.
The computed actual speed value is then set to zero, which means that all actual speed
value messages and output signals no longer provide any useful information.
116
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
Drive functions