Siemens SINAMICS S120 Function Manual page 798

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Communication
10.3 Communication via PROFINET IO
Configuring the F-CPU in HW Config
1. Different than for a drive control, now select a PROFIsafe-compatible controller, for
2. To establish communication, you must again select PROFINET IO.
Figure 10-59 PROFIsafe controller configuration
3. In HW Config, click "Station\Save and compile".
4. Click the S120 component in the drive control window.
5. Start copying with "Edit\Copy".
6. Return to the HW Config window of the PROFIsafe controller.
7. Right-click the PROFINET line.
796
example, a CPU 317F-2 PN/DP. We have manually renamed the PROFIsafe controller to
be "F-CPU".
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
Drive functions