Control of the Basic Functions via PROFIsafe (CU310-2 and CU320-2)
The following table lists the response times from receiving the PROFIsafe telegram at the
Control Unit up to initiating the particular response.
Table 9- 3
Response times when controlling via PROFIsafe
Function
STO
SBC
SS1 (time-controlled)
Selection until STO is initiated
SS1 (time-controlled)
Selection until SBC is initiated
SS1 (time-controlled)
Selection until braking is initiated
The specified response times involve internal SINAMICS response times. Program run times
in the F host and the transmission time via PROFIBUS or PROFINET are not taken into
account. When calculating the response times between the F-CPU and the converter, you
must take into account that faults in the communication can result in a safety function only
being selected after the PROFIsafe monitoring time (F_WD_Time) has expired. The
PROFIsafe monitoring time (F_WD_Time) must also be included in the calculation when an
error occurs.
Drive functions
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
Typical
5 x r9780 + t_K
1)
6 x r9780 + t_K
1)
5 x r9780 + p9652 + t_K
1)
6 x r9780 + p9652 + t_K
1)
5 x r9780 + 2 ms + t_K
1)
Safety Integrated basic functions
9.7 Response times
Worst case
5 x r9780 + t_K
1)
10 x r9780 + t_K
1)
5 x r9780 + p9652 + t_K
1)
10 x r9780 + p9652 + t_K
4 x r9780 + 2 ms + t_K
1)
1)
587