Parameter
p8839
Description:
Values:
For p8839, the following rules apply:
● The setting of p8839 applies for all drive objects of a Control Unit (device parameter).
● For the setting p8839[0] = 99 and p8839[1] = 99 (automatic assignment, factory setting),
● An alarm is issued if the same hardware (Control Unit onboard or COMM BOARD) is
● If the CAN module (CBC10) is used, the entry of p8839[0] = 2 is not permissible (no
● If p8839[x] is set to 2, and the COMM BOARD is missing/defective, then the
Overview of important parameters (see SINAMICS S120/S150 List Manual)
• p0922
• p0978[0...24]
• p8815[0...1]
• p8839[0...1]
• p9601
Drive functions
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
PZD Interface hardware assignment
Assigning the hardware for cyclic communication via PZD interface 1 and interface
2.
0: Inactive
1: Control Unit onboard
2: COMM BOARD
99: Automatic
the hardware used is automatically assigned to interfaces IF1 and IF2. Both indices must
be selected so that the automatic assignment is activated. If both indices are not
selected, then an alarm is output and the setting p8839[x] = 99 is treated just like
'inactive'.
selected in p8839[0] and p8839[1]. Then the setting of p8839[0] is valid, and the setting of
p8839[1] is treated just like 'inactive'.
assignment of the CAN module to IF1). An alarm is then issued.
corresponding interface is not automatically supplied from the Control Unit onboard
interface. Message A08550 is output instead.
IF1 PROFIdrive PZD telegram selection
List of drive objects
IF1/IF2 PZD functionality selection
PZD Interface hardware assignment
SI enable functions integrated in the drive (Control Unit)
10.1 Communication according to PROFIdrive