Communication
10.1 Communication according to PROFIdrive
Example, central probe evaluation
Assumptions for the example:
● Determination of the time stamp MT1_ZS_S by evaluating the rising edge of probe 1
● Determination of the time stamp MT2_ZS_S and MT2_ZS_F by evaluating the rising and
● Probe 1 on DI/DO 9 of the Control Unit (p0680[0] = 1)
● Probe 2 on DI/DO 10 of the Control Unit (p0680[1] = 2)
● Manufacturer-specific telegram p0922 = 391 is set.
10.1.2.8
Motion Control with PROFIdrive
The "Motion Control with PROFIBUS" or "Motion Control with PROFINET" function can be
used to implement an isochronous drive coupling between a master and one or more slaves
via the PROFIBUS fieldbus or an isochronous drive coupling via PROFINET.
Note
The isochronous drive coupling is defined in the following documentation:
Reference: /P5/ PROFIdrive Profile Drive Technology
696
falling edge of probe 2
Figure 10-13 Flow diagram: Central probe example
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
Drive functions