Monitoring and protective functions

8.2 Thermal monitoring and overload responses

8.2
Thermal monitoring and overload responses
The thermal power unit monitor is responsible for identifying critical situations. If alarm
thresholds are exceeded, the user can set parameterizable response options that enable
continued operation (e.g. with reduced power) and prevent immediate shutdown. The
parameterization options, however, only enable intervention below the shutdown thresholds,
which cannot be changed by the user.
The following thermal monitoring functions are active:
● I
● Heat-sink temperature - A05000 - F30004
● Chip temperature - A05001 - F30025
If an overload occurs with respect to any of these three monitoring functions, an alarm is first
output. The alarm threshold p0294 (I
shutdown (trip) values.
Example
The temperature difference between two sensors must not exceed more than 15 Kelvin (K);
a temperature difference of 5 K is set for the temperature monitoring of the heat sink and the
air intake. This means that 15 K or 5 K below the shutdown threshold an alarm is issued
regarding the pending overtemperature. Using p0294, it is only possible to change the alarm
threshold so that an alarm is received earlier. This means that an intervention can then be
made in the drive process (e.g. reduce the load, reduce the ambient temperature).
530
t monitoring - A07805 - F30005
2
I
t monitoring is used to protect components that have a high thermal time constant
2
compared with semiconductors. An overload with regard to I
converter load r0036 is greater than 100% (load in % in relation to rated operation).
Is used to monitor the temperature r0037.0 of the heat sink on the power semiconductors
(IGBT).
Significant temperature differences can occur between the IGBT barrier junction and the
heat sink. The calculated barrier junction temperature is displayed in r0037[13...18]; the
monitoring ensures that the specified maximum barrier junction temperature is not
exceeded.
t monitoring) can be parameterized relative to the
2
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
t is present when the
2
Drive functions