If p1213 is set lower than the sum of p1212, the magnetization time r0346 and the additional
delay time due to flying restart, then fault F07320 is generated at each restart. p1210 = 1
prevents a restart The monitoring time must be extended if the faults that occur cannot be
immediately and successfully acknowledged (e.g. when faults are permanently present).
Commissioning
1. Activate the function for drive object VECTOR and X_INF (all drive objects "Infeed"; i.e.
2. Set the startup attempts (p1211).
3. Set the wait times (p1212, p1213).
4. Check the function.
Exceptions
There are faults, where after they have occurred, an automatic restart would be dangerous
or is undesirable. Enter the numbers of these faults into p1206[0...9]. The automatic restart is
suppressed if one of these faults occurs. After the cause of the fault has been removed, the
drives must be switched-on in another way.
Overview of important parameters (see SINAMICS S120/S150 List Manual)
• r0863.0...2
• p1206[0...9]
• p1207
• p1208
• p1210
• p1211
• p1212
• p1213
• r1214.0...15
Drive functions
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
A_INF, B_INF, S_INF).
– Automatic restart: Set mode (p1210).
– Flying restart: Activate function (p1200).
CO/BO: Drive coupling status word / control word
Faults without automatic restart
BI: Automatic restart (AR) - connection to the following drive object
BI: Automatic restart modification, infeed
Automatic restart mode
Automatic restart, startup attempts
Automatic restart, delay time startup attempts
Automatic restart monitoring time
CO/BO: Automatic restart status
Basic functions
6.10 Automatic restart
289