Safety Integrated basic functions
9.2 General information
Note
PROFIsafe or TM54F
Using a Control Unit, control is possible either via PROFIsafe or TM54F. Mixed operation is
not permissible.
9.2.4

Parameter, Checksum, Version, Password

Properties of Safety Integrated parameters
The following applies to Safety Integrated parameters:
● They are kept separate for each monitoring channel.
● During startup, checksum calculations (Cyclic Redundancy Check, CRC) are performed
● Data storage: The parameters are stored on the non-volatile memory card.
● Factory settings for safety parameters
● They are password-protected against accidental or unauthorized changes.
566
on the safety parameter data and checked. The display parameters are not contained in
the CRC.
– A reset of the safety parameters to the factory setting on a drive-specific basis using
p3900 and p0010 = 30 is only possible when the safety functions are not enabled
(p9301 = p9501 = p9601 = p9801 = p10010 = 0).
– Safety parameters can be reset to the factory setting with p0970 = 5. To do so, the
Safety Integrated password must be set. When Safety Integrated is enabled, this can
result in faults, which in turn require an acceptance test to be performed. Then save
the parameters and carry out a POWER ON.
– A complete reset of all parameters to the factory settings (p0976 = 1 and p0009 = 30
on the Control Unit) is possible even when the safety functions are enabled (p9301 =
p9501 = p9601 = p9801 = p10010 ≠ 0).
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3