Communication
10.4 Communication via SINAMICS Link
Note
For double words, two PZD must be read in succession. Read a 32-bit setpoint that is at
PZD 2+PZD 3 of the telegram from node 2, and map this to PZD 2+PZD 3 of node 1:
p8872[1] = 2, p8870[1] = 2, p8872[2] = 2, p8870[2] = 3
Activation
To activate SINAMICS Link connections, perform a POWER ON for all nodes. The
assignments of p2051[x]/2061[2x] and the links of the read parameters r2050[x]/2060[2x]
can be changed without a POWER ON.
10.4.4

Example

Task
Configure SINAMICS Link for two nodes and transfer the following values:
● Send data from node 1 to node 2
● Send data from node 2 to node 1
Procedure
1. For all nodes, set p0009 = 1 to change the device configuration.
2. For all nodes, for the CBE20, set the SINAMICS Link mode:
3. Assign the node numbers for the devices involved:
4. For both nodes p0009 = 0, carry out "Copy RAM to ROM" followed by a POWER ON.
5. Set all CBE20 to the isochronous mode by setting p8812[0] = 1.
6. Limit the maximum number of nodes with p8811 = 16.
7. For both nodes p0009 = 0, carry out a "Copy RAM to ROM" followed by a POWER ON in
810
– r0898 CO/BO: Control word, sequence control, drive 1 (1 PZD), in the example PZD 1
– r0079 CO: Total torque setpoint (2 PZD), in the example PZD 2
– r0021 CO: Smoothed actual speed (2 PZD), in the example PZD 3
– r0899 CO/BO: Status word, sequence control, drive 2 (1 PZD), in the example PZD 1
– p8835 = 3
– Node 1: p8836 = 1 and
– Node 2: p8836 = 2
order to activate the modified firmware versions and the new settings in the CBE20.
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
Drive functions