6.28 Web server
4. Enter the new parameter value in the "New Value" input field. Then click "Submit" to
5. Click "RAM TO ROM".
6.28.10

Updating the firmware or configuration

Series commissioning via the Web server
You can load a firmware or a configuration to the memory card of the drive with the aid of the
Web server (see Updating firmware/configuration on the memory card (Page 364)).
One of the most important applications for the configuration update is the series
commissioning via the duplication of a master configuration. The individual steps are listed in
the following:
Sequence
1. Configure the master machine (STARTER offline and also online).
2. Switch STARTER offline.
3. Execute the "Load to file system" function.
4. Download the master configuration via the Web browser on the other drives (cloning).
402
confirm the input.
If this value is not possible or not permitted, the dialog box remains open. A message text
is also displayed.
When the entry of a parameter value is successful, the dialog box is closed. The new
parameter value is displayed in the parameter list.
The changed parameter values must be saved to the memory card of the drive. After a
parameter value has been changed, the "RAM TO ROM" button is highlighted in color.
The RAM content is backed up with all changes made to the parameter values. The
backup can take several seconds.
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
Drive functions