11.4 DCC axial winder
Limitation of the speed controller output with dynamic speed limits
r1538
r1534
p1552
r1535
p1554
Figure 11-9
Adaptation of the torque limits by means of tension controller
This method is often used in winder applications to prevent the winder from running away if
the web breaks.
For this purpose, the drive can be operated with an overdriven speed controller. In so doing,
the speed setpoint is calculated as a function of the diameter (see DCA block). The control
signal of the tension controller is set to the torque limits. This means that in normal operation
the drive operates at the torque limit. In case of a web break, this prevents the tension
controller from actively building torque. The winder speed is limited by the speed setpoint.
830
r1539
Limitation of the speed controller output with dynamic speed limits (example of SERVO)
See 6060 for VECTOR application.
1
p1551
r0899.5
[5060 .4]
1
0
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
0
[5060 .7]
[5610.3]
r1509
+
[5060 .7]
Drive functions