Infeed
1.1 Active Infeed
1.1.8
Harmonics controller
Harmonics in the line voltage cause harmonics in the line currents. Current harmonics can
be reduced by activating the harmonics controller.
Example: Setting the harmonics controller
The 5th and 7th harmonics are to be compensated:
Table 1- 4
Index
[0]
[1]
The phase currents in parameter p0069[0..2] (U, V, W) can be checked using the STARTER trace
function.
Overview of important parameters (see SINAMICS S120/S150 List Manual)
• p3624[0...1]
• p3625[0...1]
• r3626[0...1]
• r0069[0...6]
38
Example parameters for the harmonics controller
p3624
5
7
Infeed harmonics controller order
Infeed harmonics controller scaling
Infeed harmonics controller output
Phase current actual value
p3625
100%
100%
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
Drive functions