7.11 Extended stop and retract
7.11.4

ESR responses

7.11.4.1

Extended stopping

In the case of a fault, the objective is to stop the drive in a defined fashion. The stopping
method is used as long as the drive is still capable of functioning. The function is
parameterized and operates on an axis-specific basis. Axes are not coupled.
Configuring the "Extended stop" response
1. The stop response is configured with the parameter setting p0888 = 1.
2. Set the time in parameter p0892 for which the last setpoint from r1438 is frozen before
3. Select the OFF ramp with parameter p0891.
520
braking is initiated.
Figure 7-28
OFF ramp with timer
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3