Design the transformer for the following loads:
● Max. dU/dt stress at the inverter input terminals: 6 kV/µS
● Peak voltage load phase-phase and phase-ground: 8.4 kV
● Current load with DC component: approx. 4 A to 5 A
3.5.10

Actual value acquisition

Actual current and voltage values are recorded by the AVT combination module
combination module converts analog signals into digital signals and forwards them to the PSA.
The signals are transferred to the PSA via fiber-optic cables.
Figure 3-5
The AVT combination is installed in the power unit.
3.5.11

Common power supply

3.5.11.1

Field of application

The common power supply (GSV) is an AC/AC converter that converts an alternating voltage
into a square-wave voltage.
The square-wave voltage of 55 V generated from the input voltage supplies four power outputs
with equality of access.
Each power output is monitored for undervoltage. When the voltage level of all power outputs
is within the standard range, the LED signaling the status indication lights up green. The device
switches itself off automatically in the event of a short-circuit at one of the power outputs. The
associated LED of the affected power output lights up red until the short-circuit has been
rectified and the device is back in proper working order. This requires that the upstream
miniature circuit-breaker is opened and after approximately 10 seconds is closed again.
SINAMICS SM150 6SL3845-2NN41-8AD2
Operating Instructions Rev.201910281310 EXAMPLE
AVT combination module
3.5 Description of the components
Description
. The AVT
39