Parameters Changed By Motor Code Selection (For Pm Motors); Parameters Changed By Motor Code Selection (For Pm Motors); Yaskawa Smra Series Spm Motor - YASKAWA Z1000U Series Programming Manual

Hvac matrix low harmonic drive for hvac applications
Hide thumbs Also See for Z1000U Series:
Table of Contents

Advertisement

A.19 Parameters Changed by Motor Code Selection (for PM Motors)
The following tables show parameters and default settings that change with the motor code selection E5-01 when Open Loop
Vector for PM motors is used.
u

Yaskawa SMRA Series SPM Motor

Table A.14 200 V, 1800 r/min Type Yaskawa SMRA Series SPM Motor Settings
No.
Name
Motor Code Selection (for PM Motors)
Voltage Class
E5-01
Rated Power
Rated Speed
E5-02
Motor Rated Power (for PM Motors)
E5-03
Motor Rated Current (for PM Motors)
E5-04
Number of Motor Poles (for PM Motors)
Motor Stator Resistance (r1) (for PM
E5-05
Motors)
Motor d-Axis Inductance (Ld) (for PM
E5-06
Motors)
Motor q-Axis Inductance (Lq) (for PM
E5-07
Motors)
Motor Induction Voltage Constant 1 (Ke)
E5-09
(for PM Motors)
Motor Induction Voltage Constant 2 (Ke)
E5-24
(for PM Motors)
E1-04
Maximum Output Frequency
E1-05
Maximum Voltage
E1-06
Base Frequency
E1-09
Minimum Output Frequency
Table A.15 200 V, 3600 r/min Type Yaskawa SMRA Series SPM Motor Settings
No.
Name
Motor Code Selection (for PM Motors)
Voltage Class
E5-01
Rated Power
Rated Speed
E5-02
Motor Rated Power (for PM Motors)
E5-03
Motor Rated Current (for PM Motors)
E5-04
Number of Motor Poles (for PM Motors)
Motor Stator Resistance (r1) (for PM
E5-05
Motors)
Motor d-Axis Inductance (Ld) (for PM
E5-06
Motors)
Motor q-Axis Inductance (Lq) (for PM
E5-07
Motors)
Motor Induction Voltage Constant 1 (Ke)
E5-09
(for PM Motors)
Motor Induction Voltage Constant 2 (Ke)
E5-24
(for PM Motors)
E1-04
Maximum Output Frequency
E1-05
Maximum Voltage
E1-06
Base Frequency
E1-09
Minimum Output Frequency
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
A.19 Parameters Changed by Motor Code Selection (for PM Motors)
Unit
0002
V
200
kW
0.4
r/min
1800
kW
0.4
A
2.1
8
Ω
2.47
mH
12.7
mH
12.7
mVs
0
/rad
mV/
62.0
(r/min)
Hz
120
V
200.0
Hz
120
Hz
6
Unit
0103
V
200
kW
0.75
r/min
3600
kW
0.75
A
4.1
8
Ω
0.538
mH
3.2
mH
3.2
mVs
0
/rad
mV/
32.4
(r/min)
Hz
240
V
200.0
Hz
240
Hz
12
Default Settings
0003
0005
200
200
0.75
1.5
1800
1800
0.75
1.5
4.0
6.9
8
8
1.02
0.679
4.8
3.9
4.8
3.9
0
0
64.1
73.4
120
120
200.0
200.0
120
120
6
6
Default Settings
0105
0106
200
200
1.5
2.2
3600
3600
1.5
2.2
8.0
10.5
8
8
0.20
0.15
1.3
1.1
1.3
1.1
0
0
32.7
36.7
240
240
200.0
200.0
240
240
12
12
0006
0008
200
200
2.2
3.7
1800
1800
2.2
3.7
10.8
17.4
8
8
0.291
0.169
3.6
2.5
3.6
2.5
0
0
69.6
72.2
120
120
200.0
200.0
120
120
6
6
0108
200
3.7
3600
3.7
16.5
8
0.097
1.1
1.1
0
39.7
240
200.0
240
12